What You Need to Know: Meeting Specialty Fire Hydrant Flow Requirements

Every jurisdiction has fire protection codes and requirements for new construction and remodels.  Many require only that you follow the International Fire Code and have signed sealed hydraulic calculations, but others have their own requirements. 

Alternatives in Engineering can help you with signed sealed hydraulic calculations and any unique requirements a jurisdiction can throw at us.

Here are some examples of unique requirements around the country:

City of Austin Fire Protection Rule requires the following:

For hydrant flow calculations, follow Appendix B of 2012 IFC but limit reduction of fire flow to 50% for certain building types

Accepted “C” values for calculations are 110 for PVC & Copper 80 otherwise

Austin Water also requires General Construction Notes and project information on drawings.

Port St. Lucie, FL requires the following in stamped sealed calculations: Continue reading “What You Need to Know: Meeting Specialty Fire Hydrant Flow Requirements” »